NORMES
CARACTÉRISTIQUES ET AVANTAGES
The D0 Linocur® is a combination of switch disconnector fuse and Neozed® 63A fuse-link, equiped with significant safety characeristics and sophisticated switching and terminal technology.
The power dissipation of Neozed® fuse-links leads to internal heating in the Linocur® device. Special design measures have been implemented in the development of Linocur® in order to prevent the device from overheating and avoid the unwanted, premature operation of the fuse-link:
- generously sized, solid copper strip conductors
- highly sprung foot contact
- wide area of heat transfer through contact with the screw cap
- wide area of contact at the foot contact
- special contacts which share functions
Thanks to this design, Linocur® features one of the lowest power dissipation values on the market for D0 fuse-combination units devices.
Plus de caractéristiquesApplications
Documents & Ressources
Fiches techniques
Compliance
Numéro d'article
M1012609
Numéro de catalogue
05861.020000
Description
Interrupteur-sectionneur DIN D0 Linocur® Taille D02 440VAC 20A 1 pôle avec fusibles et pièces de calibre fixes , largeur 26.60mm
Code EAN / UPC
3605340495942
Fréquence
50 ... 60 Hz
Tension nominale AC CEI
440 V
Courant assigné
20 A
AC ou DC
AC
Taille du fusible
D02
Détails de conception
with fuse-links and fixed gauge pieces
Nombre de pôles
1-Pole
Couple nominal
3.5 N m
Installation de montage
Rail DIN conf. EN 60715
Poids du produit
0.2133 kg
Largeur du produit
26.60 mm
Longueur du produit
70.00 mm
Hauteur du produit
90.00 mm
Quantité du pack de vente
3 EA
Poids du pack de vente
0.6399 kg
Largeur du pack de vente
85.00 mm
Longueur du pack de vente
100.00 mm
Hauteur du pack de vente
75.00 mm