NORMES
CARACTÉRISTIQUES ET AVANTAGES
Mersen HP15NH photovoltaic (PV) fuse serie was engineered and designed specifically for the protection of photovoltaic systems. Helio-Protection® HP15NH fuse links are designed for the protection of cables in a PV group of chains when a short circuit occurs in a panel (main fuse category). This HelioProtection® main fuse range enlarges our PV fuse links offering on 1XL/2XL/3L sizes having a worldwide acceptance. They are of the gPV type and comply with both IEC 60269-6 and UL 2579 PV standards.
They are available with plain blades, bolted blades for direct mounting with and without striker.
Applications
Documents & Ressources
Fiches techniques
Compliance
Numéro d'article
F1057223
Numéro de catalogue
HP15NH3LPV400BI
Description de l'objet (ERP)
1500VDC NH3L gPV 400A Bolt C/P
Description
NH fuse-link gPV, 1500VDC, size 3L, 400A, for direct mounting, with striker
Code EAN / UPC
3605340593266
Tension nominale DC UL
1500 V
Tension nominale DC CEI
1500 V
Courant assigné
400 A
AC ou DC
DC
Vitesse/Caractéristique
gPV
Taille du fusible
3L
Montage
Montage direct
Pouvoir de coupure DC nominal maximal
150 kA @ 1500 V, L/R = 3 ms
Dissipation au courant nominal
71 W
Dissipation thermique à la valeur de courant intermédiaire
28 W @ 0.7 In W
Système d'indication
Oui
Type de système d'indication
Percuteur
Connexion / Matériel terminal
Cuivre argenté
Type de Connexion / Borne
Couteaux type DIN
Poids du produit
1.66 kg
Largeur du produit
113.00 mm
Longueur du produit
205.00 mm
Hauteur du produit
74.00 mm
Quantité du pack de vente
1 EA
Poids du pack de vente
1.66 kg
Largeur du pack de vente
115.00 mm
Longueur du pack de vente
230.00 mm
Hauteur du pack de vente
105.00 mm